The Beluk 3TA162H2-EB22B-03 (1250521) is a thyristor controller engineered specifically for switching capacitors. Operating on a mains voltage of 480 V at 50/60 Hz, this unit features a rated current of 150 A and delivers a stepped output of 125 kvar at 480 V with the actuator in the outer conductor. Two phases are switched during operation. The device requires a supply voltage and fan voltage of 120 V, 50/60 Hz, alongside a control signal of 8 - 30 V DC. Designed for vertical installation at an installation height under 1000 m, it utilizes forced AF cooling and accommodates a temperature range of -10 to 60 °C, with power reduction required above 45 °C. The controller measures 260 x 160 x 215 mm in height, width, and depth, and incorporates a maximum 160 mA inertial hedging.
For customized pricing and availability, please fill out ourcontact formor give us a call. We are dedicated to providing solutions that align with your specific requirements.
How can I access 3TA162H2-EB22B-03 / 1250521 catalogs, user manuals, technical documents, and PDFs?
Do you provide technical support for 3TA162H2-EB22B-03 / 1250521?
While we do not offer direct technical support, we can assist you in contacting the manufacturer to ensure you receive the support you need.
| Manufacturer | Beluk |
|---|---|
| Country | |
| Part number | 3TA162H2-EB22B-03 / 1250521 |
| Inner Code | 4231680 |
| Custom Code | 85365003 |
| Product type | Thyristor controller for switching capacitors |
|---|---|
| Part number | 3TA162H2-EB22B-03 / 1250521 |
| Stepped output | 125 kvar at 480 V |
| Mains voltage | 480 V, 50/60 Hz |
| Rated current | 150 A |
| Supply voltage | 120 V, 50/60 Hz |
| Fan voltage | 120 V, 50/60 Hz |
| Control signal | 8 - 30 V DC |
| Temperature range | -10 - 60 °C |
| Cooling | Forced AF |
| Installation height | < 1000 m |
| Installation | Vertical |
| Dimensions | 260 x 160 x 215 mm H x W x D |
| Hedging | Maximum 160 mA (inertial) |