UKM 52 Potential Transformer by CGS
Get a quote
The CGS UKM 52 is an indoor potential transformer designed for a frequency of 60 Hz and built to comply with IEC 61869-3 standards. It features an insulation level of 41.5/85/200 kV and a voltage factor of 1.9 x One 8 h. The unit includes two windings: the first winding delivers a performance and precision of 50 VA at Class 0.5, while the second winding provides 50 VA at Class 3P. Its transformation ratio is specified as 34500: √3/115: √3 - 115:3 V - V. Engineered for operation in standard indoor environments, this CGS potential transformer functions within an ambient temperature range of -5°C to +40°C and at altitudes below 1000 m. Overall dimensions and spatial requirements correspond to outline drawing IT2120X, part 41033, 31034.
More CGS part numbers
Frequently Asked Questions(FAQ):
Where can I buy UKM 52 by CGS in the USA?
You can purchase UKM 52 by CGS from PAOParts LLC. We serve customers across the USA, offering competitive prices and reliable service.
What is the price of the UKM 52?
Price and availability are quoted per request. Send the part number and the quantity you need through our quote request form and you will receive a written offer by e-mail.
Who is the official distributor or seller of CGS in the United States?
While we are not the official distributor or seller of CGS in the United States, we source our products from reliable channels and offer you original CGS equipment at competitive prices.
How can I access UKM 52 catalogs, user manuals, technical documents, and PDFs?
Ask for them in your quote request. We attach the datasheet, catalogue page or manual we hold for UKM 52 to our written reply.
Do you provide technical support for UKM 52?
While we do not offer direct technical support, we can assist you in contacting the manufacturer to ensure you receive the support you need.
Characteristics
| Manufacturer | CGS |
|---|---|
| Part number | UKM 52 |
| Inner Code | 4652602 |
Technical specification
| Product type | Indoor Potential Transformer |
|---|---|
| Insulation Level | 41.5/85/200 kV |
| Type | Indoor |
| Transformation Ratio | 34500: √3/115: √3 - 115:3 V - V |
| Performance/Precision (1st winding) | 50 VA/Cl. 0.5 |
| Performance/Precision (2nd winding) | 50 VA/Cl 3P |
| Voltage Factor | 1.9 x One 8 h |
| Frequency | 60 Hz |
| Ambient Temperature | -5°C... +40°C |
| Altitude | < 1000 m |
| Conformity | Standard IEC 61869-3 |
| Outline Drawing | IT2120X, part 41033, 31034 |