The CGS UKP 24/3 is an indoor resin-insulated voltage transformer designed to comply with IEC 61869-3 standards. Featuring an insulation level of 24/50/125 kV, this TV model operates at a frequency of 50 Hz with a transformation ratio of 15000: √3/110: √3 - 110:3 * V-V. It delivers a performance and accuracy of 50 VA/CL 3P and 30 VA/CL 3P, alongside a voltage factor of 1.9 x Un for 30 seconds. Built for indoor environments, the UKP 24/3 functions within an ambient temperature range of -5°C to +40°C and at altitudes under 1000 m. Overall dimensions and structural layouts correspond to Annex IT1313X, part. 41033 and 31032.
For customized pricing and availability, please fill out ourcontact formor give us a call. We are dedicated to providing solutions that align with your specific requirements.
How can I access UKP 24/3 (24,0/50,0/3,0/125kV) catalogs, user manuals, technical documents, and PDFs?
Do you provide technical support for UKP 24/3 (24,0/50,0/3,0/125kV)?
While we do not offer direct technical support, we can assist you in contacting the manufacturer to ensure you receive the support you need.
| Manufacturer | CGS |
|---|---|
| Country | |
| Part number | UKP 24/3 (24,0/50,0/3,0/125kV) |
| Inner Code | 4773538 |
| Product type | indoor resin voltage transformer |
|---|---|
| TV model | UKP 24/3 |
| Insulation | in resin |
| Insulation level | 24/50/125 kV |
| Type | for indoor |
| Transformation ratio | 15000: √3/110: √3 - 110:3 * V-V |
| Performance/accuracy | 50 VA/CL 3P, 30 VA /CL 3P |
| Voltage factor | 1.9 x Un 30 s |
| Frequency | 50 Hz |
| Ambient temperature | -5°C... +40°C |
| Altitude | < 1000 m |
| Compliance | IEC 61869-3 standards |
| Overall drawing | Annex IT1313X, part. 41033, 31032 |