The Cleveland AFS-145 is an Air Pressure Sensing Switch engineered for reliable air pressure monitoring. This pressure switch features a versatile mount position, allowing installation with the diaphragm in any vertical plane. It offers a set point range from 0.05 ± 0.02" w.c. to 12.0" w.c. (1.27 mm w.c. ± 0.508 mm w.c. to 304.8 mm w.c., or 0 to 0.43 psi) and withstands a maximum pressure of ½ psi (0.03 bar). Designed to perform in demanding environments, the AFS-145 operates within a temperature range of -40F to 180F (-40 to 82C). For electrical connectivity, it provides an electrical rating of 300 VA pilot duty at 115 to 277 VAC, along with 15 amps noninductive to 277 VAC at 60 Hz.
For customized pricing and availability, please fill out ourcontact formor give us a call. We are dedicated to providing solutions that align with your specific requirements.
How can I access AFS-145 catalogs, user manuals, technical documents, and PDFs?
Do you provide technical support for AFS-145?
While we do not offer direct technical support, we can assist you in contacting the manufacturer to ensure you receive the support you need.
| Manufacturer | Cleveland |
|---|---|
| Country | |
| Part number | AFS-145 |
| Inner Code | 189793 |
| Custom Code | 8708990000 |
| Product type | Air Pressure Sensing Switch |
|---|---|
| Mount Position | Mount with the diaphragm in any vertical plane |
| Set Point Range | 0.05 ± 0.02" w.c. to 12.0" w.c. (1.27 mm w.c. ± 0.508 mm w.c to 304.8 mm w.c.) (0 to 0.43 psi) |
| Maximum Pressure | ½ psi (0.03 bar) |
| Operating Temperature Range | -40F to 180F (-40 to 82C) |
| Electrical Rating | 300 VA pilot duty at 115 to 277 VAC, 15 amps noninductive to 277 VAC, 60 Hz |