127-5600 universal transformer U-UL by SBA

127-5600

Get a quote

Condition : New (Unused)

Price: On request

Delivery: On request

QR code for this PAOParts product page

The SBA 127-5600 universal transformer U-UL is a 5600/16300 VA isolation and isolating transformer designed for 50-60 Hz frequencies. Built with a pri-sek IIIi0 switching group and complete vacuum-impregnated resin surface treatment, this unit features an insulation class of ISC 155 (F) and operates in continuous duty mode S1 (DB) with an ambient temperature rating of TA=50 degrees C (CSA: 40 degrees C). It provides input voltages from 200 to 550 V through 10 mm² input terminals (UT 10:1.5-1.8 Nm) and dual 115 V output voltages via 16 mm² output terminals (UT 16:2.5-3 Nm), delivering an output current of 24.3 A per output with a 3.8% short circuit voltage. Designed for horizontal mounting on foot brackets, the part measures 237 x 375 x 190 mm, offers IP 00/IPxxB protection class I, and carries UL and CSA approvals according to VDE 0570, EN 61558-2-2/-4, UL 5085, and CSA C22.2 No.66 standards.

More SBA part numbers

See all SBA products

Frequently Asked Questions(FAQ):


Where can I buy 127-5600 by SBA in the USA?

You can purchase 127-5600 by SBA from PAOParts LLC. We serve customers across the USA, offering competitive prices and reliable service.


What is the price of the 127-5600?

Price and availability are quoted per request. Send the part number and the quantity you need through our quote request form and you will receive a written offer by e-mail.


Who is the official distributor or seller of SBA in the United States?

While we are not the official distributor or seller of SBA in the United States, we source our products from reliable channels and offer you original SBA equipment at competitive prices.


How can I access 127-5600 catalogs, user manuals, technical documents, and PDFs?

Ask for them in your quote request. We attach the datasheet, catalogue page or manual we hold for 127-5600 to our written reply.


Do you provide technical support for 127-5600?

While we do not offer direct technical support, we can assist you in contacting the manufacturer to ensure you receive the support you need.

Characteristics

Manufacturer SBA
Part number 127-5600
Inner Code 4624246
Custom Code 85043200

Technical specification

Product type Universal isolating transformer
Power 5600/16300 VA
Input voltage 200/220/240/360/380/400/420/440/460/480/500/530/550 V
Output voltage I 115 II 115 V
Output current 24.3 A
Frequency 50-60 Hz
Winding type isolation transformer/isolating transformer
Short circuit voltage 3.8 %
Switching group Pri-Sek IIIi0
Surface treatment complete vacuum-impregnated resin/resin coated
Protection class IP 00/IPxxB//I
Input connections Terminals 10 mm² (UT 10:1.5-1.8 Nm)
Output connections Terminals 16 mm² (UT 16:2.5-3 Nm)
Mounting on foot brackets horizontally/horizontally on mounting brackets
Standard VDE 0570/EN 61558-2-2/-4/UL 5085/CSA C22.2 No.66
UL file approvals E250288
CSA file 255319
Insulation class ISC 155 (F)
Operating mode TA=50°C (CSA: 40°C)/S1 (DB)
Dimensions W x D x H 237 x 375 x 190 mm
Need a price?Send your part numbers — written offer with lead time.