The BFI Automation 3001N is a 2-channel flame monitor designed for reliable flame detection when used with BFI flame sensors. Operating on a 24V DC supply voltage, this 19" plug-in module features an analog display with a bar graph and status LEDs to provide output signals and pre-alarms for both the burner management system and the operator. It supports redundant sensor operation and delivers a potential-free fail-safe relay output for flame ON/OFF status, alongside a 0/4 to 20 mA analog output indicating flame quality. Operators benefit from high customizability, including two adjustable sensitivity settings and two adjustable switch-off times ranging from 0.2 to 6 seconds, both of which are selectable via remote signal. Additionally, the unit features an adjustable switch-on delay and threshold.
See all BFI AUTOMATION products
For customized pricing and availability, please fill out ourcontact formor give us a call. We are dedicated to providing solutions that align with your specific requirements.
How can I access 3001N catalogs, user manuals, technical documents, and PDFs?
Do you provide technical support for 3001N?
While we do not offer direct technical support, we can assist you in contacting the manufacturer to ensure you receive the support you need.
| Manufacturer | BFI AUTOMATION |
|---|---|
| Country | |
| Part number | 3001N |
| Inner Code | 5285904 |
| Custom Code | 84169000 |
| Product type | 2-Channel Flame Monitor |
|---|---|
| Part Number | 3001N |
| Manufacturer Part Number | 6020-3001-03 |
| Type | Flame Monitor 3001N |
| Display | Analog Display, Bar graph for mA output |
| Channels | 2-Channel |
| Form Factor | 14TE, 3U (19" plug-in module) |
| Outputs | Fail-safe relay output (potential-free), Analog output 0/4 ... 20 mA |
| Switch-off times | 0.2 - 6 s (2 adjustable, selectable via remote signal) |
| Sensitivity settings | 2 adjustable (selectable via remote signal) |
| Supply voltage | 24V DC |