3001N FLAME AMPLIFIER BFI by BFI AUTOMATION

3001N

Get a quote

Condition : New (Unused)

Price: On request

Delivery: On request

QR code for this PAOParts product page

The BFI Automation 3001N is a 2-channel flame monitor designed for reliable flame detection when used with BFI flame sensors. Operating on a 24V DC supply voltage, this 19" plug-in module features an analog display with a bar graph and status LEDs to provide output signals and pre-alarms for both the burner management system and the operator. It supports redundant sensor operation and delivers a potential-free fail-safe relay output for flame ON/OFF status, alongside a 0/4 to 20 mA analog output indicating flame quality. Operators benefit from high customizability, including two adjustable sensitivity settings and two adjustable switch-off times ranging from 0.2 to 6 seconds, both of which are selectable via remote signal. Additionally, the unit features an adjustable switch-on delay and threshold.

More BFI AUTOMATION part numbers

See all BFI AUTOMATION products

Frequently Asked Questions(FAQ):


What is the price of the 3001N?

For customized pricing and availability, please fill out ourcontact formor give us a call. We are dedicated to providing solutions that align with your specific requirements.


While we are not the official distributor or seller ofBFI AUTOMATIONin the United States, we source our products from reliable channels and offer you originalBFI AUTOMATIONequipment at competitive prices.

How can I access 3001N catalogs, user manuals, technical documents, and PDFs?


You can access catalogs, user manuals, and technical documents for3001Non our website. Visit our resources section or contact us directly for specific documents.

Do you provide technical support for 3001N?


Do you provide technical support for 3001N?

While we do not offer direct technical support, we can assist you in contacting the manufacturer to ensure you receive the support you need.

Characteristics

Manufacturer BFI AUTOMATION
Country
Part number 3001N
Inner Code 5285904
Custom Code 84169000

Technical specification

Product type 2-Channel Flame Monitor
Part Number 3001N
Manufacturer Part Number 6020-3001-03
Type Flame Monitor 3001N
Display Analog Display, Bar graph for mA output
Channels 2-Channel
Form Factor 14TE, 3U (19" plug-in module)
Outputs Fail-safe relay output (potential-free), Analog output 0/4 ... 20 mA
Switch-off times 0.2 - 6 s (2 adjustable, selectable via remote signal)
Sensitivity settings 2 adjustable (selectable via remote signal)
Supply voltage 24V DC