The BFI Automation 6013-2063-00 (CFC2000IR2-L) OE converter is a two-channel compact system designed for the continuous monitoring of gas and oil burners of any capacity. Featuring a semiconductor dual sensor with separately adjustable spectral sensitivity in the UV and IR ranges, it incorporates advanced frequency analysis for improved selectivity. The system includes electronic self-monitoring for safe operation, alongside LED indicators for flame intensity and flame relay status. Housed in an IP66 aluminum housing painted in RAL5010, the unit connects to a BFI fiber optic cable or lance and operates at an ambient temperature range of -20 to +70°C. Settings such as sensitivity, ON/OFF level, and switch-on delay are software-configured, while the safety switch-off time is set via a jumper and software (1-5s). Data transmission utilizes an RS232/infrared interface.
See all BFI AUTOMATION products
For customized pricing and availability, please fill out ourcontact formor give us a call. We are dedicated to providing solutions that align with your specific requirements.
How can I access 6013-2063-00 - CFC2000IR2-L catalogs, user manuals, technical documents, and PDFs?
Do you provide technical support for 6013-2063-00 - CFC2000IR2-L?
While we do not offer direct technical support, we can assist you in contacting the manufacturer to ensure you receive the support you need.
| Manufacturer | BFI AUTOMATION |
|---|---|
| Country | |
| Part number | 6013-2063-00 - CFC2000IR2-L |
| Inner Code | 4902932 |
| Custom Code | 84169000 |
| Product type | CFC2000IR2-L OE converter flame monitor |
|---|---|
| Supply voltage | 24V DC |
| Current consumption | approx. 200 mA |
| Spectral range | 300-2700nm |
| Viewing angle | 2.7° |
| Self-test | once in 800ms |
| Ambient temperature | -20 to + 70°C |
| Data transmission | RS232/infrared interface |
| Electrical connection | Harting plug 90° |
| Dimension | L120xW122xH80 mm |
| Housing | Aluminum, RAL5010, IP66 |
| ATEX zone2 | I 3G Ex ec nC II T4 Gc |
| Safety Integrity Level | SIL3 |
| Flame signal output | 0/4-20mA (Ra <250 Ohm) |
| Flame relay switching voltage | max. 48V |
| Flame relay switching current | max. 1A |
| Flame relay switching capacity | max. 30W |