The BFI Automation 6013-2063-22 is an OE Converter CFC2000IR2-L dual-channel compact system designed for the continuous monitoring of gas and oil burners of any power output. Featuring frequency analysis for enhanced selectivity, this unit utilizes a semiconductor sensor with a spectral range covering UV, VIS, and IR. It includes electronic self-monitoring executing once every 800ms, LED indicators for flame intensity and relay status, and a housing made of aluminum finished in RAL5010 with an IP66 rating. Settings such as the safety shutdown time (1-5s), sensitivity, ON/OFF level, and switch-on delay are configured via software, while online frequency analysis and visualization are supported using BFI software. The unit operates on a 24V DC supply voltage, features a 0/4-20mA flame signal output and a potential-free changeover contact flame relay, and connects via a 90° Harting connector. Built for demanding environments, it holds ATEX Zone 2 certification and a SIL3 safety rating.
See all BFI AUTOMATION products
For customized pricing and availability, please fill out ourcontact formor give us a call. We are dedicated to providing solutions that align with your specific requirements.
How can I access 6013-2063-22 catalogs, user manuals, technical documents, and PDFs?
Do you provide technical support for 6013-2063-22?
While we do not offer direct technical support, we can assist you in contacting the manufacturer to ensure you receive the support you need.
| Manufacturer | BFI AUTOMATION |
|---|---|
| Country | |
| Part number | 6013-2063-22 |
| Inner Code | 5290576 |
| Custom Code | 84169000 |
| Product type | OE Converter CFC2000IR2-L Compact Flame Detector |
|---|---|
| Output | Relay and 0/4-20mA |
| Max. switching voltage | 48V |
| Max. switching current | 1A |
| Max. switching power | 30W |
| Flame signal output | 0/4-20mA (Ra <250 Ohm) |
| Supply voltage | 24V DC |
| Current consumption | approx. 200 mA |
| Spectral range | 300-2700nm |
| Viewing angle | 2.7° |
| Self-test | once every 800ms |
| Ambient temperature | -20 to +70°C |
| Data transmission | RS232/infrared interface |
| Electrical connection | Harting connector 90° |
| Dimensions | L 235 x W 108 x H 190 mm |
| Housing | Aluminum, RAL5010, IP66 |
| ATEX Zone 2 | II 3G Ex ec nC II T4 Gc |
| SIL | SIL3 |