DS12-230/G by Citel
Get a quote
The Citel DS12-230/G is a 2-pole (1+1) surge protective device engineered with varistor technology. Classified as a Type 3 (Class D) arrester, this unit operates at a nominal voltage of 230/400 V and provides a protection level (Up) of 1.0 kV. It delivers a maximum discharge surge current (Imax) of 20 kA or 10 kA based on the 8/20µs waveform. Designed for fast operation, the DS12-230/G features a rapid response time of under 20 ns and generates no follow current (If). This plug-in unit has a compact installation dimension of 2 modular units (2 TE) and is supplied without a remote signaling contact.
More Citel part numbers
Frequently Asked Questions(FAQ):
Where can I buy DS12-230/G by Citel in the USA?
You can purchase DS12-230/G by Citel from PAOParts LLC. We serve customers across the USA, offering competitive prices and reliable service.
What is the price of the DS12-230/G?
Price and availability are quoted per request. Send the part number and the quantity you need through our quote request form and you will receive a written offer by e-mail.
Who is the official distributor or seller of Citel in the United States?
While we are not the official distributor or seller of Citel in the United States, we source our products from reliable channels and offer you original Citel equipment at competitive prices.
How can I access DS12-230/G catalogs, user manuals, technical documents, and PDFs?
Ask for them in your quote request. We attach the datasheet, catalogue page or manual we hold for DS12-230/G to our written reply.
Do you provide technical support for DS12-230/G?
While we do not offer direct technical support, we can assist you in contacting the manufacturer to ensure you receive the support you need.
Characteristics
| Manufacturer | Citel |
|---|---|
| Part number | DS12-230/G |
| Inner Code | 1703777 |
Technical specification
| Product type | 2-pole Type 3 surge protector |
|---|---|
| Pole count | 2-pole (1+1) |
| Technology | Varistor |
| Arrester type | Type 3 (Class D) |
| Nominal voltage | 230/400 V |
| Protection level Up | 1.0 kV |
| Max. discharge surge current Imax | 20 kA / 10 kA (8/20μs) |
| Follow current If | None |
| Response time | <20 ns |
| Installation dimensions | 2 TE, pluggable |
| Remote signaling contact | None |